Discussion in 'CNC Mills/Routers' started by robin lawrie, Apr 26, 2021.

  1. robin lawrie

    Builder

    Joined:
    Mar 19, 2021
    Messages:
    87
    Likes Received:
    10
    I understand that "pigtails" on the end of a cable shield are a no-go, however inside the huanyang vfd connection area its all plastic, so nowhere to clamp the shield end... Just an earth screw terminal which i read (somewhere) you should connect both the vfd earth wire and also the shield (which necessitates a pigtail) ..?

    Any tips appreciated
     
  2. Kevon Ritter

    Kevon Ritter Veteran
    Builder

    Joined:
    Apr 30, 2015
    Messages:
    597
    Likes Received:
    294
    Don't connect the Spindle wire shield to the VFD. A shield is meant to be grounded directly. The earth on the VFD is also grounded.

    Unless you are talking about the 110/220V input? If so, then you have Line, Neutral, and Earth. That cable wouldn't be shielded.
     
  3. robin lawrie

    Builder

    Joined:
    Mar 19, 2021
    Messages:
    87
    Likes Received:
    10
    No im talking about the vfd/spindle cable.

    So, since i wish to shield as much of the cable as possible, i should clamp the shield to the backplate of the metal case just before it enters the vfd? Or run a seperate cable to the star ground from the shield end?
    (metal case has a star grounding point/block where everything goes, bolted in the opposite corner to the vfd)
     
  4. Kevon Ritter

    Kevon Ritter Veteran
    Builder

    Joined:
    Apr 30, 2015
    Messages:
    597
    Likes Received:
    294
    Solder on some extra wire to the shield as close to the VFD as possible. I'll get a pic of mine when the sun comes up.
     
    Peter Van Der Walt likes this.
  5. robin lawrie

    Builder

    Joined:
    Mar 19, 2021
    Messages:
    87
    Likes Received:
    10
    Thank you. Any clarification appreciated!
     
  6. robin lawrie

    Builder

    Joined:
    Mar 19, 2021
    Messages:
    87
    Likes Received:
    10
    Ive ordered some tinned copper braid to make diy "shield clamps" for the ends of all the shielded cables.. For some reason actual steel "p" shaped clamps like ive seen on google are extremely hard to find and overpriced, so ill just lay cable with shield exposed on backplate of enclosure, lay a couple cm of copper braid over it perpendicular to the cable, then screw it down on both sides with washers..

    If you have any photos or schematics of what "works" i would love to see them (no rush, when sun comes up is fine )
     
  7. Kevon Ritter

    Kevon Ritter Veteran
    Builder

    Joined:
    Apr 30, 2015
    Messages:
    597
    Likes Received:
    294
    I completely forgot...
    Black, red, and white are the three spindle wires. Green has a connector for spindle ground. Then the shield would be wired to earth ground.
     