XYZ Probe Plus with VFDs and other ground-loop inducing components

Discussion in 'General Talk' started by juansierra, Apr 24, 2020.

  1. sergiomajluf

    sergiomajluf Well-Known
    Builder

    Joined:
    Jun 2, 2020
    Messages:
    44
    Likes Received:
    37
    I've had the sme issue since always, but learnt to live with it. Basically I unplug my VFD whenever I needed to probe (mostly in the middle of jobs, changing bits)... which is cumbersome and feels unstable, because every once in a while my controller crashes when doing this ... until...


    I just tried my very same cnc/controller/vfd/probe setup, except this time with my laptop, unplugged from the AC mains and voila!

    Time to get a USB optoisolator then.

    edit: BTW, and this might help other diagnose the problem. I had another issue, the trackpad of my cnc computer was unstable too. Didn't give it much thought asuming it was just "airborne" EMI from the VFD. Well, I just changed the laptop power supply's cable to an unearthed one, and problem begone. Time to resucitate my intent of having home swithces too!
     
    #61 sergiomajluf, Apr 12, 2022
    Last edited: Apr 12, 2022
    sharmstr and Peter Van Der Walt like this.
  2. JonnyO

    JonnyO New
    Builder

    Joined:
    Aug 8, 2020
    Messages:
    3
    Likes Received:
    1
    I had the same problem with my XYZ probe using an HP SFF PC. When I switched back to an old Surface Pro 3 it had no problems at all. Picked up a USB in-line isolator and everything has been problem-free ever since.

    Thanks to everyone that contributed to this thread, most of all to Peter for putting up with all of us. :)
     
    Peter Van Der Walt likes this.
  3. Joe D

    Joe D New
    Builder

    Joined:
    Feb 14, 2019
    Messages:
    19
    Likes Received:
    15
    I have an X32 Blackbox that has similar problems. I have been using it for a few months now and it was all working fine. Now my XYZ Plus probe has the green LEDS on any time the ground wire is touching the spindle. I have disconnected everything from the Blackbox except for the Power plug, the Probe plug and the Computer connection to my laptop. If I disconnect the computer cord then the green LEDS go out. Im believing there might be a short in the Blackbox. I have also completely replaced every wire including the wires from the VFD, all the motor wires, all the limit switch wires and the computer connection wire. I had changed nothing from when it was all working and when it started failing.
    Thanks for any help.
     
  4. Peter Van Der Walt

    Peter Van Der Walt OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Mar 1, 2017
    Messages:
    15,307
    Likes Received:
    4,361
    That rather indicates a short through the PC - try a different PC, or if the computer has 2-pin power plug - try flipping it around.
     
  5. Adam Jelinek

    Builder

    Joined:
    Jan 24, 2023
    Messages:
    47
    Likes Received:
    3
    I don't understand the grounding of ac and dc. With my spindle am I not to ground it to the vfd?
     
  6. Peter Van Der Walt

    Peter Van Der Walt OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Mar 1, 2017
    Messages:
    15,307
    Likes Received:
    4,361
    Spindle should be EARTHED

    DC GND should be a seperate domain

    Having a short between the two (thats supposed to be isolated from each other - high voltage mains vs low voltage DC) is dangerous.


    Unplug things one at a time until probe (good test, could use a multimeter too but probe is a quick indicator of a problem) until problem clears up. Could be endstops mounted incorrectly, failing PSU in a desktop PC or Monitor, etc
     
  7. Adam Jelinek

    Builder

    Joined:
    Jan 24, 2023
    Messages:
    47
    Likes Received:
    3
    Unplugging the usb from my laptop turned the probe off. Unplugged each motor limits witch didn't change anything.
     
  8. Peter Van Der Walt

    Peter Van Der Walt OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Mar 1, 2017
    Messages:
    15,307
    Likes Received:
    4,361
    Then laptop PSU might have a short. Try on battery only.
    Try flipping 2-pin plug on laptop PSU in socket (Neutral Earth bonds exists, if plugged in wrong way round it might leak current)
     
  9. Adam Jelinek

    Builder

    Joined:
    Jan 24, 2023
    Messages:
    47
    Likes Received:
    3
    The laptop only had a 2 prong plug. Will try battery only
     
  10. Peter Van Der Walt

    Peter Van Der Walt OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Mar 1, 2017
    Messages:
    15,307
    Likes Received:
    4,361
    making it easy to reverse live/neutral, try plugging it in 180deg from current orientation
     
  11. Adam Jelinek

    Builder

    Joined:
    Jan 24, 2023
    Messages:
    47
    Likes Received:
    3
    It doesn't come apart at all. With it unplugged it still have the probe lights on. So I'm assuming a usb insulator would be needed. Now. With the vfd grounded to the outlet. Where would the proper place to ground the cnc it's self? Can I go to an outlet ground at well?
     
    #71 Adam Jelinek, Aug 27, 2024
    Last edited: Aug 27, 2024
  12. Adam Jelinek

    Builder

    Joined:
    Jan 24, 2023
    Messages:
    47
    Likes Received:
    3
    Issure resolved. Wasn't my usb. I had 2 limit switch grounding out through the bolt. Added a small plastic spacer and all is good
     
  13. Adam Jelinek

    Builder

    Joined:
    Jan 24, 2023
    Messages:
    47
    Likes Received:
    3
    Am I understanding this correctly. The ground for the spindle should be an earth ground and not a ground to the ground lug on the vdf?
     
  14. Peter Van Der Walt

    Peter Van Der Walt OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Mar 1, 2017
    Messages:
    15,307
    Likes Received:
    4,361
    Confirm with your VFD and spindle vendor about specifics, but usually both spindle body and VFD has an Earth (connected to mains earth)

    Low voltage components has DC GND

    And DC GND should be perfectly isolated from Mains Earth
     
  15. Wackimac

    Wackimac New
    Builder

    Joined:
    Dec 8, 2016
    Messages:
    3
    Likes Received:
    1
    I am guessing I am having the same problem with my prob.
     

    Attached Files:

  16. Peter Van Der Walt

    Peter Van Der Walt OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Mar 1, 2017
    Messages:
    15,307
    Likes Received:
    4,361
    I see steel rails, Z axis not isolated from frame like wheels would be so you have a wider area to check for DC GND (from say a limit switch) shorting to the frame or some other AC EARTH to DC GND short.
     
  17. Wackimac

    Wackimac New
    Builder

    Joined:
    Dec 8, 2016
    Messages:
    3
    Likes Received:
    1
    After check everything I found that I had a bad wire on my Y limit switch. It had a very low ohms reading between the red and black wires, Replaced wire and the XYZ prob work just fine. Also all limit switches as well work. This is my second machine I have build with OpenBuild and I am still learning. Thanks Doug
     
    Peter Van Der Walt likes this.
  18. ryana14

    ryana14 New
    Builder

    Joined:
    Tuesday
    Messages:
    4
    Likes Received:
    0
    I have this exact issue. Afer testing I found DC ground in the controller is connecting to Spindle Earth via the V- out from the CNC Controller (CNC4Newbie C4N controller, Openbuilds touch plate) to the ACM terminal (Analog Signal Reference: ACM acts as the common ground for analog inputs) on the Huanyang 2.2 KW spindle. This is wired as per instructions and works as it should, but please let me know if there is a better way to connect controller to VFD, see my connection below. The spindle is earthed back to the VFD so that completes the circuit and therefore the Probe PIN connects when the magnate is on the tool. (Edit: I think erroneous conclusion above).

    I swapped Signal and GND (blue with black) on the probe and now it works when the tool touches the plate, no need for the magnate.


    I have CNC Controller to VFD wired as follows.
    CNC Controller SP Relay + -------- FOR
    CNC Controller SP Relay - -------- DCM
    CNC Controller 0-10V + -------- VI
    CNC Controller 0-10V - -------- ACM

    The CNC Controller 0-10V terminal is continuous with the controller Probe - terminal
     
    #78 ryana14, Jan 14, 2025 at 3:46 PM
    Last edited: Jan 14, 2025 at 5:06 PM
  19. Peter Van Der Walt

    Peter Van Der Walt OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Mar 1, 2017
    Messages:
    15,307
    Likes Received:
    4,361
    On VFDs the inputs like ACM is isolated from AC GND, so probably not via the ACM port


    Workaround fine, but there is still a short somewhere, i'd try fixing it before it causes damage
     
  20. ryana14

    ryana14 New
    Builder

    Joined:
    Tuesday
    Messages:
    4
    Likes Received:
    0
    Thanks for the reply, I just doubled checked with the multimeter, on my Huanyang VFD ACM is not continuous (multimeter does not beep) with AC ground on the VFD. I'll investigate further.
     
    #80 ryana14, Jan 14, 2025 at 4:20 PM
    Last edited: Jan 14, 2025 at 4:39 PM
  21. ryana14

    ryana14 New
    Builder

    Joined:
    Tuesday
    Messages:
    4
    Likes Received:
    0
    I think I found it.
    Testing continuity between controller DC ground to Spindle Earth.
    1: Controller Plugged in and VFD plugged in: I get Continuity, multimeter beeps.
    2: Controller Plugged in, VFD not plugged in. No continuity.
    3: Controller not Plugged in, VFD plugged in. No continuity.

    Is this a ground loop? Initially I thought impossible because my controller has no earth coming in, only the two 24V wires from the AC to 24 V DC power supply. The VFD is US/Canada (Three wires total, no neutral) 240 V with earth.

    I'm obviously missing something? Thanks for the help.
     
    #81 ryana14, Jan 14, 2025 at 5:02 PM
    Last edited: Jan 14, 2025 at 5:53 PM
  22. ryana14

    ryana14 New
    Builder

    Joined:
    Tuesday
    Messages:
    4
    Likes Received:
    0
    I solved the issue, my old power supply was connecting the DC Ground to AC Mains Earth, I connected a MEAN WELL LRS-350-24 350.4W 24V and the issue went away, I can now use the probe wired in the normal way.
     
  23. Peter Van Der Walt

    Peter Van Der Walt OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Mar 1, 2017
    Messages:
    15,307
    Likes Received:
    4,361
    Oh yes please, not worth risking BlackBox on anything less :) - using different PSU can void warranty
     
    ryana14 likes this.