Discussion in 'Control Software' started by Mallardduck31, Nov 1, 2019.

  1. Mallardduck31

    Builder

    Joined:
    Sep 27, 2019
    Messages:
    40
    Likes Received:
    3
    Started running a large 3D carving the other day and when about 3/4 of the way through the system locked up stating limits had been exceeded. I had run the “check size” function before I kicked off the project and all as good.

    I had re-homed and restarted the project. It proceeded to almost the exact same spot and stopped again but this time when I tried to re-go e the z axis dove deep into the material and into the bed! Ugh!

    Once I got the bit out and system re-homed again I started the project yet a third time. This time I noticed the 3D viewer location and actual tool were no where near in synch. I stopped and went to the work zero and the tool was off by about 3 inches in the Y axis from the original work zero.

    How can the work zero coordinates be lost? Why did the tool stop in almost the same position two times and then dig deep into the material when trying to re-home?

    The system has worked flawlessly since I assembled and got running about two weeks ago.
     
  2. Alex Chambers

    Alex Chambers Master
    Moderator Builder

    Joined:
    Nov 1, 2018
    Messages:
    2,784
    Likes Received:
    1,364
    Hi @Mallardduck31, a bit more info please - what machine, controller and control software?
    Alex.
     
  3. Mallardduck31

    Builder

    Joined:
    Sep 27, 2019
    Messages:
    40
    Likes Received:
    3
    Workbee 1010 with Blackbox and using Open build software.
     
  4. David the swarfer

    David the swarfer OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Aug 6, 2013
    Messages:
    3,460
    Likes Received:
    1,915
    please post your gcode file (here or direct to me) and I will ruin it through my testbed and see if there is any problem with the gcode.
     
  5. Peter Van Der Walt

    Peter Van Der Walt OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Mar 1, 2017
    Messages:
    15,050
    Likes Received:
    4,313
    Grbl will also present that error to you when your limits have a false trigger event (EMI, loose wiring, etc)

    Which switches do you have? These: OpenBuilds BlackBox 4X Documentation or the better ones these: OpenBuilds BlackBox 4X Documentation (The Xtension Limits have built in filtering to largely avoid false triggers - if you don't have them, its a worthy and cheap upgrade: Xtension Limit Switch Kit
     
  6. Mallardduck31

    Builder

    Joined:
    Sep 27, 2019
    Messages:
    40
    Likes Received:
    3
    I do remember that the system did give me an error message stating limits had been exceeded.

    I am running the Open builds limit switches that came with the kit.

    Should I re route the limit switch wiring outside the cable carrier to eliminate the risk of false triggers?

    I will send over the gcode later this morning.
     
  7. Peter Van Der Walt

    Peter Van Der Walt OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Mar 1, 2017
    Messages:
    15,050
    Likes Received:
    4,313
    Over the years there were two types, check the two links I posted above to see which type you have. The newer ones are more resilient, but even so, EMI is a strange thing and sometime just moving a wire out of the way is enough to cure it.
     
  8. Mallardduck31

    Builder

    Joined:
    Sep 27, 2019
    Messages:
    40
    Likes Received:
    3
    I have the newer ones. I am rerunning the job this morning and it’s been going for about 45 minutes without an issue so far.
     
    Peter Van Der Walt likes this.
  9. Mallardduck31

    Builder

    Joined:
    Sep 27, 2019
    Messages:
    40
    Likes Received:
    3
    Job completed in a little over 4 hours and no issues.
    It must have been EMI. I did not make any changes to the wiring location at this time. I will keep an on on things and if it acts up a second time I will reroute the wires.
     
  10. David the swarfer

    David the swarfer OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Aug 6, 2013
    Messages:
    3,460
    Likes Received:
    1,915
    reroute NOW, it will happen again. the simple rule is that power (wires to the steppers) and signals (wires to the limit switches) must not be close together. and the power cord to the router motor must definitely be away from all signal wires including the USB cable.
     
    MaryD and Peter Van Der Walt like this.
  11. Mallardduck31

    Builder

    Joined:
    Sep 27, 2019
    Messages:
    40
    Likes Received:
    3
    Sound advice. How far from power cables should they be? Is outside the cable carrier far enough?
     
  12. David the swarfer

    David the swarfer OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Aug 6, 2013
    Messages:
    3,460
    Likes Received:
    1,915
    good question. I don't think it will need to be very far since the magnetic field falls off with the (roughly) inverse square of the distance, ie, it falls off rapidly.
    so, an inch may be enough if other wiring rules have been followed like star grounding and pullup resistors on the limit pins (the Blackbox has that already).
     
    Peter Van Der Walt likes this.
  13. Paul Stoller

    Paul Stoller Journeyman
    Builder

    Joined:
    Feb 28, 2016
    Messages:
    157
    Likes Received:
    107
    Does this mean that the build instructions (electronics) for the Sphinx are in error. The electronics build video had us running the limit switch cables in the same drag chain as the stepper cables.
     
  14. Peter Van Der Walt

    Peter Van Der Walt OpenBuilds Team
    Staff Member Moderator Builder Resident Builder

    Joined:
    Mar 1, 2017
    Messages:
    15,050
    Likes Received:
    4,313
    Not really. EMI is a bit like magic, 99% of you guys will have no issues. Something is just a little different in some environments and the risk goes up.
    BlackBox has several features to mitigate EMI (never entirely, but as good as we can)
     
  15. Alex Chambers

    Alex Chambers Master
    Moderator Builder

    Joined:
    Nov 1, 2018
    Messages:
    2,784
    Likes Received:
    1,364
    As @Peter Van Der Walt said emi is unlikely to cause problems. When it does it can be very puzzling and on rare occasions seriously damaging. I run my stepper cables in the drag chain with my limit switch wiring and have had no issues at all (Duet Controller - like the black box has interference suppression built in to the limit switch circuitry) but I would definitely keep mains wiring or VFD-spindle wiring well away from any low voltage stuff.
    Alex.
     
    Paul Stoller likes this.
  16. Paul Stoller

    Paul Stoller Journeyman
    Builder

    Joined:
    Feb 28, 2016
    Messages:
    157
    Likes Received:
    107
    @Peter Van Der Walt, @Alex Chambers Okay, that makes sense. I won't worry about it unless I run into issues. I obtained VFD specific cable for my spindle, it has a more flexible outer jacket, internal strain reliefs and both braided and foil shielding. I was hoping to use this in the drag chain thinking the extra shielding would be enough to prevent EMI issues. It sounds like this may be a bad idea even with the extra shielding. What is the suggestion for the spindle cable to keep it out of the way if not run through a drag chain.
     
  17. Alex Chambers

    Alex Chambers Master
    Moderator Builder

    Joined:
    Nov 1, 2018
    Messages:
    2,784
    Likes Received:
    1,364
    I clamped a bit of 2" * 1" to the side of my bench, fixed a large cup-hook to the top and hung my router cable from that. Made sure I had enough slack in the cable to reach all corners of the machine. Not elegant but it works.
    Alex.
     