That no-name PSU might not be isolating AC from DC and might damage BlackBox in ways not covered by warranty - may be wiring fault elsewhere, and...
AC EARTH to DC Ground short - should be seperate domains, somewhere in your wiring you have a short between the two.
Grbl settings backup for review as well as pics of wiring please
Contact the store to get the correct cable: Support > New Ticket The new Interface has a 4 pin connector as well for backwards compatibility....
Yeah didn't guess that one, the big yellow sticker is usually a good clue (:
Disconnect spindle. Measure voltage output from Blackbox . Use CONTROL's tool menu. At 10% should be +-1v. At 20% +-2v etc up to 10v at 100% See...
Then check the PSU. To move a motor you need the right Grbl Settings (double check you did use CONTROL V1.0.370, did remember to save and did...
Additional or extended settings Most of these, defaults are just fine. Only time we ever change $34 is when you use a RC Servo as a Toolhead:...
Did you remember to load a machine profile from Grbl Settings tab > Select machine from the list > Save and reset when prompted? LEAD1515s profile...
Did you remember to load a machine profile from Grbl Settings tab > Select machine from the list > Save and reset when prompted. Even if you did,...
Mainly I'm saying avoid changing settings off guesswork without researching them. That one pops out as obviously changed from default. What else...
No, the VFD is 400hz 3-phase PWM should be default, 5000 i think it was.
Post a Grbl Settings backup for review Calibration just corrects for manufacturing tolerances, it needs a solid mechanical setup underneath....
Grbl v1.1 Configuration - just calculate theoretical steps per mm based on your mechanicals, then fine tune using CONTROL > Wizards and tools >...
Redraw it for them, or make them give you workable files that comply with docs:software:file-errors [OpenBuilds Documentation]
You can change the output in Vectric's post to be whatever you need it to be. 1000 is the default (as $30=1000 in default grbl settings) but your...
Grbl Setting = 0 (as you want 0v-10v to be 0rpm-24000rpm) settings it to something else messes up your scale The 7200 min is set on the VFD! So 0...
Sales coming up soon, sign up on Newsletter to be let know when that happens OpenBuildsPartstore.com ships internationally Shipping and Delivery...
Correct way is GND and 0-10v only, setup the VFD correctly to stop/start based on Min Freq
Either wired wrong, configured wrong, or EMI. More importantly the Door input is for a Door switch. E-stops shouldn't be connected there....